Parametry falownika Danfoss VLT MicroDrive FC51

0-** Operation/Display 6-13 Terminal 53 High Current
0-0* Basic Settings 0.01-20.00 mA *20.00 mA
0-03 Regional Settings 6-14 Term. 53 Low Ref./Feedb.
*[0] International Value
[1] US -4999-4999 *0.000
0-04 Oper. State at Power-up 6-15 Term. 53 High Ref./Feedb.
(Hand) Value
[0] Resume -4999-4999 *50.000
*[1] Forced stop, ref=old 6-16 Terminal 53 Filter Time
[2] Forced stop, ref=0 Constant
0-1* Set-up Handling 0.01-10.00 s *0.01 s
0-10 Active Set-up 6-19 Terminal 53 mode
*[1] Setup 1 *[0] Voltage mode
[2] Setup 2 [1] Current mode
[9] Multi Setup 6-2* Analog Input 2
0-11 Edit Set-up 6-22 Terminal 60 Low Current
*[1] Setup 1 0.00-19.99 mA *0.14 mA
[2] Setup 2 6-23 Terminal 60 High Current
[9] Active Setup 0.01-20.00 mA *20.00 mA
0-12 Link Setups 6-24 Term. 60 Low Ref./Feedb.
[0] Not Linked Value
*[20] Linked -4999-4999 *0.000
0-31 Custom Readout Min Scale 6-25 Term. 60 High Ref./Feedb.
0.00 - 9999.00 * 0.00 Value
0-32 Custom Readout Max Scale -4999-4999 *50.00
0.00 - 9999.00 * 100.0 6-26 Terminal 60 Filter Time
0-4* LCP Keypad Constant
0-40 [Hand on] Key on LCP 0.01-10.00 s *0.01 s
[0] Disabled 6-8* LCP Potentiometer
*[1] Enabled 6-80 LCP Potmeter Enable
0-41 [Off / Reset] Key on LCP [0] Disabled
[0] Disable All *[1] Enable
*[1] Enable All 6-81 LCP potm. Low Reference
[2] Enable Reset Only -4999-4999 *0.000
0-42 [Auto on] Key on LCP 6-82 LCP potm. High Reference
[0] Disabled -4999-4999 *50.00
*[1] Enabled 6-9* Analog Output xx
0-5* Copy/Save 6-90 Terminal 42 Mode
0-50 LCP Copy *[0] 0-20 mA
*[0] No copy [1] 4-20 mA
[1] All to LCP [2] Digital Output
[2] All from LCP 6-91 Terminal 42 Analog Output
[3] Size indep. from LCP *[0] No operation
0-51 Set-up Copy [10] Output Frequency
*[0] No copy [11] Reference
[1] Copy from setup 1 [12] Feedback
[2] Copy from setup 2 [13] Motor Current
[9] Copy from Factory setup [16] Power
0-6* Password [19] DC Link Voltage
0-60 (Main) Menu Password [20] Bus Reference
0-999 *0 6-92 Terminal 42 Digital Output
0-61 Access to Main/Quick Menu Patrz par. 5-40
w/o Password *[0] No Operation
*[0] Full access [80] SL Digital Output A
[1] LCP:Read Only 6-93 Terminal 42 Output Min
[2] LCP:No Access Scale
1-** Load/Motor 0.00-200.0% *0.00%
1-0* General Settings 6-94 Terminal 42 Output Max
1-00 Configuration Mode Scale
*[0] Speed open loop 0.00-200.0% *100.0%
[3] Process 7-** Controllers
1-01 Motor Control Principle 7-2* Process Ctrl. Feedb
[0] U/f 7-20 Process CL Feedback 1
*[1] VVCplus Resource
1-03 Torque Characteristics *[0] NoFunction
*[0] Constant torque [1] Analog Input 53
[2] Automatic Energy Optim. [2] Analog input 60
1-05 Local Mode Configuration [8] PulseInput33
[0] Speed Open Loop [11] LocalBusRef
*[2] Jak konfiguracja w par. 1-00 7-3* Process PI
1-2* Motor Data Ctrl. 7-30 Process PI Normal/
1-20 Motor Power [kW] [HP] Inverse Ctrl
[1] 0,09 kW/0,12 KM *[0] Normal
[2] 0,12 kW/0,16 KM [1] Inverse
[3] 0,18 kW/0,25 KM 7-31 Process PI Anti Windup
[4] 0,25 kW/0,33 KM [0] Disable
[5] 0,37 kW/0,50 KM *[1] Enable
[6] 0,55 kW/0,75 KM 7-32 Process PI Start Speed
[7] 0,75 kW/1,00 KM 0.0-200.0 Hz *0.0 Hz
[8] 1,10 kW/1,50 KM 7-33 Process PI Proportional Gain
[9] 1,50 kW/2,00 KM 0.00-10.00 *0.01
[10] 2,20 kW/3,00 KM 7-34 Process PI Integral Time
[11] 3,00 kW/4,00 KM 0.10-9999 s *9999 s
[12] 3,70 kW/5,00 KM 7-38 Process PI Feed Forward
[13] 4,00 kW/5,40 KM Factor
[14] 5,50 kW/7,50 KM 0-400% *0%
[15] 7,50 kW/10,00 KM 7-39 On Reference Bandwidth
[16] 11,00 kW/15,00 KM 0-200% *5%
[17] 15,00 kW/20,00 KM 8-** Comm. and Options
[18] 18,50 kW/25,00 KM 8-0* General Settings
[19] 22,00 kW/29,50 KM 8-01 Control Site
[20] 30,00 kW/40,00 KM *[0] Digital and ControlWord
1-22 Motor Voltage [1] Digital only
50-999 V *230 -400 V [2] ControlWord only
1-23 Motor Frequency 8-02 Control Word Source
20-400 Hz *50 Hz [0] None
1-24 Motor Current *[1] FC RS485
0.01-100.00 A *Zależnie od silnika 8-03 Control Word Timeout Time
1-25 Motor Nominal Speed 0.1-6500 s *1.0 s
100-9999 rpm *Zależnie od typu 8-04 Control Word Timeout
silnika Function
1-29 Automatic Motor Tuning *[0] Off
(AMT) [1] Freeze Output
*[0] Off [2] Stop
[2] Enable AMT [3] Jog
[3] Complete AMT with Rotating [4] Max. Speed
motor [5] Stop and trip
1-3* Adv. Motor Data 8-06 Reset Control Word Timeout
1-30 Stator Resistance (Rs) *[0] No Function
[Ohm] * Zależnie od danych silnika [1] Do reset
1-33 Stator Leakage Reactance 8-3* FC Port Settings
(X1) 8-30 Protocol
[Ohm] * Zależnie od danych silnika *[0] FC
1-35 Main Reactance (Xh) [2] Modbus
[Ohm] * Zależnie od danych silnika 8-31 Address
1-5* Load Indep. Setting 1-247 *1
1-50 Motor Magnetisation at 0 8-32 FC Port Baud Rate
Speed [0] 2400 Baud
0-300% *100% [1] 4800 Baud
1-52 Min Speed Norm. Magnet. *[2] 9600 Baud (aby wybrać
[Hz] magistralę FC w 8-30)
0.0-10.0 Hz *0.0Hz *[3] 19200 Baud (aby wybrać
1-55 U/f Characteristic - U magistralę Modbus w 8-30)
0-999.9 V [4] 38400 bodów
1-56 U/f Characteristic - F 8-33 FC Port Parity
0-400 Hz *[0] Even Parity, 1 Stop Bit
1-6* Load Depen. Setting [1] Odd Parity, 1 Stop Bit
1-60 Low Speed Load Compen- [2] No Parity, 1 Stop Bit
sation [3] No Parity, 2 Stop Bits
0-199% *100% 8-35 Minimum Response Delay
1-61 High Speed Load Compen- 0.001-0.5 *0.010 s
sation 8-36 Max Response Delay
0-199% *100% 0.100-10.00 s *5.000 s
1-62 Slip Compensation 8-4* FC MC protocol set
-400-399% *100% 8-43 FC Port PCD Read Configu-
1-63 Slip Compensation Time ration
Constant *[0] None Expressionlimit
0.05-5.00 s *0.10 s [1] [1500] Operation Hours
1-7* Start Adjustments [2] [1501] Running Hours
1-71 Start Delay [3] [1502] kWh Counter
0.0-10.0 s *0.0 s [4] [1600] Control Word
1-72 Start Function [5] [1601] Reference [Unit]
[0] DC hold/delay time [6] [1602] Reference %
[1] DC brake/delay time [7] [1603] Status Word
*[2] Coast/delay time [8] [1605] Main Actual Value [%]
1-73 Flying Start [9] [1609] Custom Readout
*[0] Disabled [10] [1610] Power [kW]
[1] Enabled [11] [1611] Power [hp]
1-8* Stop Adjustments [12] [1612] Motor Voltage
1-80 Function at Stop [13] [1613] Frequency
*[0] Coast [14] [1614] Motor Current
[1] DC hold [15] [1615] Frequency [%]
1-82 Min Speed for Funct. at Stop [16] [1618] Motor Thermal
[Hz] [17] [1630] DC Link Voltage
0.0-20.0 Hz *0.0 Hz [18] [1634] Heatsink Temp.
1-9*Motor Temperature [19] [1635] Inverter Thermal
1-90 Motor Thermal Protection [20] [1638] SL Controller State
*[0] No protection [21] [1650] External Reference
[1] Termistor warning [22] [1651] Pulse Reference
[2] Thermistor trip [23] [1652] Feedback [Unit]
[3] Etr warning [24] [1660] Digital Input 18,19,27,33
[4] Etr trip [25] [1661] Digtial Input 29
1-93 Thermistor Resource [26] [1662] Analog Input 53 (V)
*[0] None [27] [1663] Analog Input 53 (mA)
[1] Analog input 53 [28] [1664] Analog Input 60
[6] Digital input 29 [29] [1665] Analog Output 42 [mA]
2-** Brakes [30] [1668] Freq. Input 33 [Hz]
2-0* DC-Brake [31] [1671] Relay Output [bin]
2-00 DC Hold Current [32] [1672] Counter A
0-150% *50% [33] [1673] Counter B
2-01 DC Brake Current [34] [1690] Alarm Word
0-150% *50% [35] [1692] Warning Word
2-02 DC Braking Time [36] [1694] Ext. Status Word
0.0-60.0 s *10.0s 8-5* Digital/Bus
2-04 DC Brake Cut In Speed 8-50 Coasting Select
0.0-400.0 Hz *0.0Hz [0] DigitalInput
2-1* Brake Energy Funct. [1] Bus
2-10 Brake Function [2] LogicAnd
*[0] Off *[3] LogicOr
[1] Resistor brake 8-51 Quick Stop Select
[2] AC brake Patrz par. 8-50 * [3] LogicOr
2-11 Brake Resistor (ohm) 8-52 DC Brake Select
Min./maks./domyślnie: Zależnie od Patrz par. 8-50 *[3] LogicOr
wielkości mocy. 8-53 Start Select
2-14 Brake Voltage reduce Patrz par. 8-50 *[3] LogicOr
0 - Zależnie od wielkości mocy.* 0 8-54 Reversing Select
2-16 AC Brake, Max current Patrz par. 8-50 *[3] LogicOr
0-150% *100% 8-55 Set-up Select
2-17 Overvoltage Control Patrz par. 8-50 *[3] LogicOr
*[0] Disabled 8-56 Preset Reference Select
[1] Enabled (not at stop) Patrz par. 8-50 * [3] LogicOr
[2] Enabled 8-8* Bus communication
2-2* Mechanical Brake Diagnostics
2-20 Release Brake Current 8-80 Bus Message Count
0.00-100.0 A *0.00 A 0-0 N/A *0 N/A
2-22 Activate Brake Speed [Hz] 8-81 Bus Error Count
0.0-400.0 Hz *0.0 Hz 0-0 N/A *0 N/A
3-** Reference / Ramps 8-82 Slave Messages Rcvd
3-0* Reference Limits 0-0 N/A *0 N/A
3-00 Reference Range 8-83 Slave Error Count
*[0] Min - Max 0-0 N/A *0 N/A
[1] -Max - +Max 8-9* Bus Jog / Feedback
3-02 Minimum Reference 8-94 Bus feedback 1
-4999-4999 *0.000 0x8000-0x7FFF *0
3-03 Maximum Reference 13-** Smart Logic
-4999-4999 *50.00 13-0* SLC Settings
3-1* References 13-00 SL Controller Mode
3-10 Preset Reference *[0] Off
-100.0-100.0% *0.00% [1] On
3-11 Jog Speed [Hz] 13-01 Start Event
0.0-400.0 Hz *5.0 Hz [0] False
3-12 Catch up/slow Down Value [1] True
0.00 - 100.0% * 0.00% [2] Running
3-14 Preset Relative Reference [3] InRange
-100.0-100.0% *0.00% [4] OnReference
3-15 Reference Resource 1 [7] OutOfCurrentRange
[0] No function [8] BelowILow
*[1] Analog Input 53 [9] AboveIHigh
[2] Analog input 60 [16] ThermalWarning
[8] Pulse input 33 [17] MainOutOfRange
[11] Local bus ref [18] Reversing
[21] LCP Potentiometer [19] Warning
3-16 Reference Resource 2 [20] Alarm_Trip
[0] No function [21] Alarm_TripLock
[1] Analog in 53 [22-25] Comparator 0-3
*[2] Analog in 60 [26-29] LogicRule0-3
[8] Pulse input 33 [33] DigitalInput_18
*[11] Local bus reference [34] DigitalInput_19
[21] LCP Potentiometer [35] DigitalInput_27
3-17 Reference Resource 3 [36] DigitalInput_29
[0] No function [38] DigitalInput_33
[1] Analog Input 53 *[39] StartCommand
[2] Analog input 60 [40] DriveStopped
[8] Pulse input 33 13-02 Stop Event
*[11] Local bus ref Patrz par. 13-01 * [40] DriveS-
[21] LCP Potentiometer topped
3-18 Relative Scaling Ref. 13-03 Reset SLC
Resource *[0] Do not reset
*[0] No function [1] Reset SLC
[1] Analog Input 53 13-1* Comparators
[2] Analog input 60 13-10 Comparator Operand
[8] Pulse input 33 *[0] Disabled
[11] Local bus ref [1] Reference
[21] LCP Potentiometer [2] Feedback
3-4* Ramp 1 [3] MotorSpeed
3-40 Ramp 1 Type [4] MotorCurrent
*[0] Linear [6] MotorPower
[2] Sine2 ramp [7] MotorVoltage
3-41 Ramp 1 Ramp up Time [8] DCLinkVoltage
0.05-3600 s *3.00 s (10.00 s1)) [12] AnalogInput53
3-42 Ramp 1 Ramp Down Time [13] AnalogInput60
0.05-3600 s *3.00s (10.00s 1)) [18] PulseInput33
3-5* Ramp 2 [20] AlarmNumber
3-50 Ramp 2 Type [30] CounterA
*[0] Linear [31] CounterB
[2] Sine2 ramp 13-11 Comparator Operator
3-51 Ramp 2 Ramp up Time [0] Less Than
0.05-3600 s *3.00 s (10.00 s 1)) *[1] Approximately equals
3-52 Ramp 2 Ramp down Time [2] Greater Than
0.05-3600 s *3.00 s (10.00 s1)) 13-12 Comparator Value
3-8* Other Ramps -9999-9999 *0.0
3-80 Jog Ramp Time 13-2* Timers
0.05-3600 s *3.00 s (10.00s1)) 13-20 SL Controller Timer
3-81 Quick Stop Ramp Time 0.0-3600 s *0.0 s
0.05-3600 s *3.00 s (10.00s1)) 13-4* Logic Rules
4-** Limits/Warnings 13-40 Logic Rule Boolean 1
4-1* Motor Limits Patrz par. 13-01 *[0] False
4-10 Motor Speed Direction [30] - [32] Time-out SL 0-2
*[0] W prawo, jeśli parametr 1-00 13-41 Logic Rule Operator 1
ustawiono na sterowanie w pętli *[0] Disabled
zamkniętej [1] And
[1] W lewo [2] Or
*[2] Oba kierunki, jeśli par. 1-00 [3] And not
ustawiono na sterowanie w pętli [4] Or not
otwartej [5] Not and
4-12 Motor Speed Low Limit [Hz] [6] Not or
0.0-400.0 Hz *0.0 Hz [7] Not and not
4-14 Motor Speed High Limit [Hz] [8] Not or not
0.1-400.0 Hz *65.0 Hz 13-42 Logic Rule Boolean 2
4-16 Torque Limit Motor Mode Patrz par. 13-40 * [0] False
0-400% *150% 13-43 Logic Rule Operator 2
4-17 Torque Limit Generator Patrz par. 13-41 *[0] Disabled
Mode 13-44 Logic Rule Boolean 3
0-400% *100% Patrz par. 13-40 * [0] False
4-4* Adj. Warnings 2 13-5* States
4-40 Warning Frequency Low 13-51 SL Controller Event
0.00 - Wartość 4-41 Hz *0.0 Hz Patrz par. 13-40 *[0] False
4-41 Warning Frequency High 13-52 SL Controller Action
Wartość 4-40-400.0 Hz *400.00 Hz *[0] Disabled
4-5* Adj. Warnings [1] NoAction
4-50 Warning Current Low [2] SelectSetup1
0.00-100.00 A *0.00 A [3] SelectSetup2
4-51 Warning Current High [10-17] SelectPresetRef0-7
0.0-100.00 A *100.00 A [18] SelectRamp1
4-54 Warning Reference Low [19] SelectRamp2
-4999.000 - Wartość 4-55 [22] Run
* -4999.000 [23] RunReverse
4-55 Warning Reference High [24] Stop
Wartość 4-54 -4999.000 [25] Qstop
*4999.000 [26] DCstop
4-56 Warning Feedback Low [27] Coast
-4999.000 - Wartość 4-57 [28] FreezeOutput
* -4999.000 [29] StartTimer0
4-57 Warning Feedback High [30] StartTimer1
Wartość 4-56-4999.000 *4999.000 [31] StartTimer2
4-58 Missing Motor Phase [32] Set Digital Output A Low
Function [33] Set Digital Output B Low
[0] Off [38] Set Digital Output A High
*[1] On [39] Set Digital Output B High
4-6* Speed Bypass [60] ResetCounterA
4-61 Bypass Speed From [Hz] [61] ResetCounterB
0.0-400.0 Hz *0.0 Hz 14-** Special Functions
4-63 Bypass Speed To [Hz] 14-0* Inverter Switching
0.0 -400.0 Hz *0.0 Hz 14-01 Switching Frequency
5-1* Digital Inputs [0] 2 kHz
5-10 Terminal 18 Digital Input *[1] 4 kHz
[0] No function [2] 8 kHz
[1] Reset [4] 16 kHz (niedostępne dla M5)
[2] Coast inverse 14-03 Overmodulation
[3] Coast and reset inv. [0] Off
[4] Quick stop inverse *[1] On
[5] DC-brake inv. 14-1* Mains monitoring
[6] Stop inv 14-12 Function at mains
*[8] Start imbalance
[9] Latched start *[0] Trip
[10] Reversing [1] Warning
[11] Start reversing [2] Disabled
[12] Enable start forward 14-2* Trip Reset
[13] Enable start reverse 14-20 Reset Mode
[14] Jog *[0] Manual reset
[16-18] Preset ref bit 0-2 [1-9] AutoReset 1-9
[19] Freeze reference [10] AutoReset 10
5-10 Terminal 18 Digital Input [11] AutoReset 15
[20] Freeze output [12] AutoReset 20
[21] Speed up [13] Infinite auto reset
[22] Speed down [14] Reset at power up
[23] Setup select bit 0 14-21 Automatic Restart Time
[28] Catch up 0 - 600s * 10s
[29] Slow down 14-22 Operation Mode
[34] Ramp bit 0 *[0] Normal Operation
[60] Counter A (up) [2] Initialisation
[61] Counter A (down) 14-26 Action At Inverter Fault
[62] Reset counter A *[0] Trip
[63] Counter B (up) [1] Warning
[64] Counter B (down) 14-4* Energy Optimising
[65] ResetCounter B 14-41 AEO Minimum Magneti-
5-11 Terminal 19 Digital Input sation
Patrz par. 5-10. * [10] Reversing 40 - 75 % * 66 %
5-12 Terminal 27 Digital Input 14-9* Fault Settings
Patrz par. 5-10. * [1] Reset 14-90 Fault level[3] Trip Lock
5-13 Terminal 29 Digital Input [4] Trip with delayed reset
Patrz par. 5-10. * [14] Jog 15-** Drive Information
5-15 Terminal 33 Digital Input 15-0* Operating Data
Patrz par. 5-10. * [16] Preset ref bit 15-00 Operating Days
0 15-01 Running Hours
[26] Precise Stop Inverse 15-02 kWh Counter
[27] Start, Precise Stop 15-03 Power Ups
[32] Pulse Input 15-04 Over Temps
5-3* Digital Outputs 15-05 Over Volts
5-34 On Delay, Terminal 42 Digital 15-06 Reset kWh Counter
Output *[0] Do not reset
0.00 - 600.00 s * 0.01 s [1] Reset counter
5-35 Off Delay, Terminal 42 Digital 15-07 Reset Running Hours
Output Counter
0.00 - 600.00 s * 0.01 s *[0] Do not reset
5-4* Relays [1] Reset counter
5-40 Function Relay 15-3* Fault Log
*[0] No operation 15-30 Fault Log: Error Code
[1] Control ready 15-4* Drive Identification
[2] Drive ready 15-40 FC Type
[3] Drive ready, Remote 15-41 Power Section
[4] Enable / No warning 15-42 Voltage
[5] Drive running 15-43 Software Version
[6] Running / No warning 15-46 Frequency Converter Order.
[7] Run in range / No warning No
[8] Run on ref / No warning 15-48 LCP Id No
[9] Alarm 15-51 Frequency Converter Serial
[10] Alarm or warning No
[12] Out of current range 16-** Data Readouts 16-0* General
[13] Below current, low Status
[14] Above current, high 16-00 Control Word
[16] Below frequency, low 0-0XFFFF
[17] Above frequency, high 16-01 Reference [Unit]
[19] Below feedback, low -4999-4999 *0.000
[20] Above feedback, high 16-02 Reference %
[21] Thermal warning -200.0-200.0% *0.0%
[22] Ready, No thermal warning 16-03 Status Word
[23] Remote ready, No thermal 0-0XFFFF
warning 16-05 Main Actual Value [%]
[24] Ready, Voltage ok -200.0-200.0% *0.0%
[25] Reverse 16-09 Custom Readout
[26] Bus ok Zależnie od par. 0-31, 0-32
[28] Brake,NoWarn 16-1* Motor Status
[29] Brake ready/NoFault 16-10 Power [kW]
[30] BrakeFault (IGBT) 16-11 Power [hp]
[32] Mech.brake control 16-12 Motor Voltage [V]
[36] Control word bit 11 16-13 Frequency [Hz]
[41] Below reference, low 16-14 Motor Current [A]
[42] Above reference, high 16-15 Frequency [%]
[51] Local ref. active 16-18 Motor Thermal [%]
5-40 Function Relay 16-3* Drive Status
[52] Remote ref. active 16-30 DC Link Voltage
[53] No alarm 16-34 Heatsink Temp.
[54] Start cmd active 16-35 Inverter Thermal
[55] Running reverse 16-36 Inv.Nom. Current
[56] Drive in hand mode 16-37 Inv. Max. Current
[57] Drive in auto mode 16-38 SL Controller State
[60-63] Comparator 0-3 16-5* Ref./Feedb.
[70-73] Logic rule 0-3 16-50 External Reference
[81] SL digital output B 16-51 Pulse Reference
5-41 On Delay, Relay 16-52 Feedback [Unit]
0.00-600.00 s *0.01 s 16-6* Inputs/Outputs
5-42 Off Delay, Relay 16-60 Digital Input 18,19,27,33
0.00-600.00 s *0.01 s 0-1111
5-5* Pulse Input 16-61 Digital Input 29
5-55 Terminal 33 Low Frequency 0-1
20-4999 Hz *20 Hz 16-62 Analog Input 53 (volt)
5-56 Terminal 33 High Frequency 16-63 Analog Input 53 (current)
21-5000 Hz *5000 Hz 16-64 Analog Input 60
5-57 Term. 33 Low Ref./Feedb. 16-65 Analog Output 42 [mA]
Value 16-68 Pulse Input [Hz]
-4999-4999 *0.000 16-71 Relay Output [bin]
5-58 Term. 33 High Ref./Feedb. 16-72 Counter A
Value 16-73 Counter B
-4999-4999 *50.000 16-8* Fieldbus/FC Port
6-** Analog In/Out 16-86 FC Port REF 1
6-0* Analog I/O Mode 0x8000-0x7FFFF
6-00 Live Zero Timeout Time 16-9* Diagnosis Readouts
1-99 s *10 s 16-90 Alarm Word
6-01 Live Zero TimeoutFunction 0-0XFFFFFFFF
*[0] Off 16-92 Warning Word
[1] Freeze output 0-0XFFFFFFFF
[2] Stop 16-94 Ext. Status Word
[3] Jog 0-0XFFFFFFFF
[4] Max speed 18-** Extended Motor Data
[5] Stop and trip 18-8* Motor Resistors
6-1* Analog Input 1 18-80 Stator Resistance (High
6-10 Terminal 53 Low Voltage resolution)
0.00-9.99 V *0.07 V 0.000-99.990 ohm *0.000 ohm
6-11 Terminal 53 High Voltage 18-81 Stator Leakage
0.01-10.00 V *10.00 V Reactance(High resolution)
6-12 Terminal 53 Low Current 0.000-99.990 ohm *0.000 ohm
0.00-19.99 mA *0.14 mA  

1) Tylko dla M4 i M5